RTU560

Store code 1000
Origin EU
Type Rack
Standard IEC 61850
Interface upto 6x Serial; 2x Ethernet ports 
Protocol IEC 61850; IEC 101; IEC 104; Modbus; DNP3; IEC 103
Sizing >5000 datapoint
Category: RTU500 series | Vender: HITACHI

Contact

Product Detail

Application Specification Documents

In complex network environments you are challenged by a large amount of data. Our RTU560 is the perfect solution for various applications for automation and control.

  • The migration solution allows you to retrofit your secondary equipment with reduced investment.
  • The combination of parallel wired I/Os, serial links and IEC 61850 is efficiently feasible with our RTU560 allowing you to work with infrastructures from different generations
  • Our flexible redundancy concepts provide high availability where you need it

 Application Area

  • Transmission network substations
    • Automation of transmission substation
    • Digital substation
    • Migration
  • Electrical distribution network, primary substation
    • Automation of primary substation
    • Transformer automation and control

560CMR01 – Communication Unit

  • Central module of the RTU560 with ARM based platform
  • 2x serial communication interfaces (RS-232 or RS-485) for local/remote communication
  • 2x Ethernet interface (10/100BaseT) SD card with licenses and functions adaptable to customer requirements
  • 1 x Micro-USB interface for webserver access

560CMR02 – Communication unit

  • 2x ETH, 6 serial (RS232/485)
  • USB interface for Webserver access
  • Powerful CMU platform (factor 3-4)
  • Considerable memory (128 MB)

560PSR00

  • Input voltage 24…60 V DC
  • Output voltage: 5 and 24 V DC
  • Suitable for redundant power supply in 560MPR03/560SFR02

560PSU01

  • Input voltage 110…220 V DC
  • Output voltage: 5 and 24 V DC
  • Suitable for redundant power supply in 560MPR03/560SFR02

560BIR01 – Binary input, 16 channels, LED’s

Binary input module 560BIR01

  • (R1: 24/60VDC; R2: 110/125VDC)
  • Support of 110/125 VDC process voltage in rack mounting
  • 110/125V module

560BOR01 – Binary output, 16 channels

To be used for control of 16 binary process signals using relay contacts.

  • 16 relay contacts, 2 groups of 8 outputs with common return
  • Max. switching voltage: 150 V DC
  • Max. breaking current: 2 A @ 60 V DC

 